Specifications - 700 SoftCam II
INPUTS
Input - 4 to 20mA dc
OUTPUTS
Output 1 - 4 to 20mA dc. Maximum output load of 500 ohms.
Output 2 - Optional. Independent to output 1. 4 to 20mA dc. Maximum output load of 500 ohms.
Relay - Optional. Tagged to output with High/Low alarm facilities.
RESOLUTION
Input - 16bit A to D.
Output - 12bit D to A per output.
DATA STORAGE
Memory - The 26 function points per output are stored in internal memory. Custom options available.
AMBIENT RANGE
Temperature - 0 to 40 Deg, 90% RH (non condensing)
COMMUNICATION
RS232 - Standard  to computer. Optional RS485 communications allowing use in conjunction with our 900 series modular solutions.
CONNECTIONS
Connectors - 30 screw terminals on 6mm pitch.
ISOLATION
Complete - to all inputs/outputs.
POWER
Mains - Standard 230V 50 Hz @ 3VA max. Optional 115V  60Hz and DC versions available.
CASE
DIN - Standard DIN case in polycarbonate measuring 100mm x 75mm x 110mm.
Specialists in Measurement Instrumentation